Purpose/Aim
The application of power cables shows an increasing tendency in extra-high voltage transmission lines, but there is still a lack of experience in cable design and maintenance of 330kV-rated cables in northwest China. It is of great significance to ensure that the cable outer sheath could withstand power-frequency and energization overvoltage, and the sheath voltage limiter play a protective role without failure.
Experimental/Modeling methods
A pure cable line, an overhead-cable line under construction and an overhead-cable-overhead line in operation were selected to simulate the in-ground short circuit and multiple no-load closing, and the maximum sheath overvoltage at the insulated joint was observed. After the sheath voltage limiter is determined based on the sheath power-frequency overvoltage results, it was brought into the simulation again to verify the correctness of the selection.
Results/discussion
The sheath power-frequency overvoltage of the long-distance hybrid overhead-cable line was the severest, up to 15kV, and therefore the voltage rating of the sheath voltage limiter was required to reach 12kV. In addition, the sheath overvoltage obtained by closing the single-point grounded side was obviously larger than that of the cross-bonded side for the pure cable line. It should be noted that the sheath overvoltage of the hybrid line was significantly larger than that of the pure cable line applied with the same bonding method, which was greatly influenced by overhead line portion and number of circuits.
Conclusions
The power-frequency overvoltage and energization overvoltage imposed on the existing 330kV sheath bonding system was at a reasonable level for outer sheath insulations. The 8-12 kV sheath voltage limiter can be selected according to the specific line configurations to ensure the safe and stable operation of the cable outer sheath and the device itself.
 
关键词
sheath overvoltage, sheath bonding method, line energization
报告人
Yuqian Sheng
Xi’an Jiaotong University

稿件作者
Yuqian Sheng Xi’an Jiaotong University
Jiankang Zheng Xi’an Power Supply Bureau State Grid Shannxi Electric Power Company
Shaobin Li Xi’an Power Supply Bureau State Grid Shannxi Electric Power Company
Yang Xu Xi’an Jiaotong University
发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    09月25日

    2022

    09月29日

    2022

  • 08月15日 2022

    提前注册日期

  • 09月10日 2022

    报告提交截止日期

  • 11月10日 2022

    注册截止日期

  • 11月30日 2022

    初稿截稿日期

  • 11月30日 2022

    终稿截稿日期

主办单位
IEEE DEIS
承办单位
Chongqing University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询