Purpose/Aim
During the switching test of on-load tap-changer(OLTC), it is found that the switching process of odd-even, even-odd taps and the value of the damping resistance affect the degree of distortion of the switching current and the assessment of the breaking current and recovery voltage of the contact. In order to reasonably assess the ability of the tap changer contacts and reduce the degree of distortion of the switching current, this paper studies the effects of different switching processes and damping resistances on the switching current.
Experimental/Modeling methods
In this paper, the switching sequence model of OLTC and the switching test loop model of resonance method are built in ATP-EMTP. And the influence of different damping resistances and different switching processes of odd-even and even-odd taps on the distortion current is simulated and analyzed. Besides, the mathematical model of optimum damping resistance is proposed.
Results/discussion
When the tap changer is switched from the odd to the even gears, the sudden change of the circuit state causes a small amplitude distortion of the test phase current. When switching from the even to the odd gears, the long-arm damping resistor consumes the energy stored in the capacitor bank and the reactor bank, and the energy consumption is faster when the damping resistor has a larger resistance value.
Conclusions
(1) The switching current distortion is small when switching from odd to even gears; the switching current distortion is large when switching from even to odd gears.
(2) During the switching process, the long-arm damping resistance on the secondary side of the tap changer test transformer plays the role of consuming the energy stored in the capacitor bank and the reactor bank. The larger the damping resistance, the smaller the switching current distortion rate.
(3) An optimum damping resistance selection method is established with the current distortion rate as the objective function. When the test parameters and transition resistance values change, the same method can still be used to select the damping resistance.
 
关键词
OLTC,switching test,damping resistance
报告人
Ruoxi Wang
China Electric Power Research Institute

稿件作者
Ruoxi Wang China Electrical Power Research Institute
发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    09月25日

    2022

    09月29日

    2022

  • 08月15日 2022

    提前注册日期

  • 09月10日 2022

    报告提交截止日期

  • 11月10日 2022

    注册截止日期

  • 11月30日 2022

    初稿截稿日期

  • 11月30日 2022

    终稿截稿日期

主办单位
IEEE DEIS
承办单位
Chongqing University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询