Harmonic Assessment on Local Power Network for BESS Connection Through Transformer Tertiary Windings
编号:209 访问权限:仅限参会人 更新:2022-08-29 12:52:16 浏览:69次 口头报告

报告开始:暂无开始时间(Asia/Shanghai)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
Purpose
With the increasing demands of the energy storage intake to facilitate Net-Zero in the power network, inoperative tertiary windings of existing supergrid transformers provide opportunities to connect Battery Energy Storage System (BESS) to achieve local system services, i.e., frequency and voltage control. One major concern is the impact of BESS connection on the local network power quality, due to the appearance of power electronic devices. BESS system is connected through a transformer to the Point of Connection (POC), which is further connected to the tertiary windings through cables and transformers. To accurately assess the impact of BESS connection on local system power quality, it is necessary to conduct transient analyses with accurate modelling of the transformer. This paper aims to perform the harmonic assessment for such BESS connection application in the UK 400 kV substation and to improve the transformer transient modelling.
Modelling methods
A representative local 400 kV substation network model was modelled in ATP-EMTP. BCTRAN and Hybrid transformer models and distributed pi cable models were configured to model the 400/132/13 kV and 33/13 kV transformers and 13 kV and 33 kV cables in the substation. In order to assess the harmonic penetration in the network, a single-frequency three-phase harmonic scan from 2nd order to 50th order by harmonic current source with 5A amplitude was carried out. In addition, a reverse engineering procedure was taken to obtain an accurate high-frequency model of the 33/0.4 kV transformer, which is directly connected with the BESS, based on limited structural specification and one FRA measurement reference.
Results
The simulation results showed the harmonic penetration in the local network is dependent on the frequency of the harmonic injection, which is related to the switching frequency of the BESS. From the harmonic scan, one harmonic resonance was observed at 1.75 kHz, which showed the heaviest harmonic penetration and was possibly caused by coincidental resonance between cable capacitances and transformer leakage impedances. Nevertheless, the voltage harmonic amplitudes attenuated greatly across the transformers. The modelled 33/0.4 kV transformer successfully reproduced the FRA spectrum as to the measurement reference.
Conclusions
The transformers showed apparent suppression effects on the voltage harmonic propagation in the local network. The Total Harmonic Distortion (THD) values at the system source and load ends were below 5%. A harmonic resonance at 1.75 kHz was observed in the studied configuration, which indicates a need of careful tuning of the BESS control system to avoid this resonance frequency. The successfully established high-frequency 33/0.4 kV transformer model enables the local network model to be integrated with the BESS control system and enables more practical harmonic scenarios to be studied.
关键词
Harmonic,Battery Storage System,Transformer High Frequency Modelling,ATP-EMTP,Tertiary Winding
报告人
Shuhang Shen
University of Exeter

稿件作者
Shuhang Shen University of Exeter
Bozhi Cheng University of Exeter;University of Manchester
Yaoxian Yang University of Exeter;University of Manchester
Siyu Gao National Grid
Oliver Cwikowski National Grid
Zhongdong Wang University of Exeter;University of Manchester
发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    09月25日

    2022

    09月29日

    2022

  • 08月15日 2022

    提前注册日期

  • 09月10日 2022

    报告提交截止日期

  • 11月10日 2022

    注册截止日期

  • 11月30日 2022

    初稿截稿日期

  • 11月30日 2022

    终稿截稿日期

主办单位
IEEE DEIS
承办单位
Chongqing University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询