879 / 2022-06-30 17:08:42
Analysis of lightning protection and grounding performance of composite material tower for low voltage distribution lines
composite material tower, grounding down conductor, lightning resistance level, economica
终稿
Chunsheng ZHENG / China Petroleum and Chemical Corporation Shengli Petroleum Administration Co., Ltd. Electric Power
Zhe WANG / China Petroleum and Chemical Corporation Shengli Petroleum Administration Co., Ltd. Electric Power
Feng HUO / State Key Laboratory of Power Grid Environmental Protection, China Electric Power Research Institute
Wenyang MA / State Key Laboratory of Power Grid Environmental Protection, China Electric Power Research Institute
Mian FAN / State Key Laboratory of Power Grid Environmental Protection, China Electric Power Research Institute
Jing NAN / State Key Laboratory of Power Grid Environmental Protection, China Electric Power Research Institute
复合材料铁塔作为一种新型的输电线路铁塔,由于其绝缘性强、耐腐蚀性好、重量轻等优点,可有效降低雷击跳闸率。为了充分利用复合材料塔的绝缘性,本文在6kV复合材料塔中加入向下的地线,并以其抗雷击性能作为研究对象。根据评估指标优化塔头高度对线路雷击跳闸率的影响,最后交叉臂长度为0.4m,塔高为10.9m,塔头高度为0.6m。给出了不同跨度和不同接地闪光密度接地电阻下的塔参数的合理组合