Partial Discharge Measurement with Non-Intrusive Broadband RF Sensors in the Fabrication Inspection of an 800 kV HVDC Converter Transformer
Non-Intrusive,Fabrication Inspection,VHF/UHF,800 kV HVDC Converter Transformer,Partial Discharge (PD) detection,Partial Discharge (PD) location,PD on-line monitoring
终稿
Jianguo Wei / Global Energy Interconnection Research Institute Europe GmbH
Hui Huang / State Grid Smart Grid Research Institute Co., Ltd
Yi Liu / Wuhan NARI LLC of SGEPRI
Zhihao Yang / State Grid Smart Grid Research Institute Co., Ltd.
Benjamin Schubert / Global Energy Interconnection Research Institute Europe GmbH
Weilin Liu / Global Energy Interconnection Research Institute Europe GmbH
Existing experimental studies using an external radio frequency (RF) antenna to detect leaked partial discharge (PD) signals from transformer are commonly carried out in a controlled lab environment with a cabinet of reduced size. In this contribution, broadband RF sensors in the very-high frequency (VHF) and ultra-high frequency (UHF) range are distributed outside an 800 kV HVDC converter transformer in its fabrication inspection for PD measurement. Results show that leaked PD signals can be successfully detected and discriminated from persistent background interferences at the test site. The capability of the developed broadband RF pulse detection and analyzing system has been demonstrated and its effectiveness for non-intrusive continuous on-line PD monitoring has been verified in fabrication inspection scene.
重要日期
  • 会议日期

    09月25日

    2022

    09月29日

    2022

  • 08月15日 2022

    提前注册日期

  • 09月10日 2022

    报告提交截止日期

  • 11月10日 2022

    注册截止日期

  • 11月30日 2022

    初稿截稿日期

  • 11月30日 2022

    终稿截稿日期

主办单位
IEEE DEIS
承办单位
Chongqing University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询