Study of Oscillation Phenomenon Caused by High-voltage Cable and No-load Transformer in the Process of De-energizing
transformer,breaker opening,ATP-EMTP,de-energizing,oscillation
终稿
Liang Tang / Hebei Fengning Pumped Storage Co., Ltd., Fengning 068350, China
Wei Wang / State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing P.R.China,102206
Guo-wen Hao / State Grid Xinyuan Company LTD., Beijing P.R. China, 100761
Lei Wang / China Electric Power Research Institute; Wuhan 430074; China;; Hubei Province
Long Chang / State Grid Xinyuan Company LTD., Beijing P.R. China, 100761
Cong Zhou / Hebei Fengning Pumped Storage Co., Ltd., Fengning 068350, China
Wei-xing Han / State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources; North China Electric Power University; Beijing P.R. China; 102206;
Hao Liu / State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources; North China Electric Power University; Beijing P.R. China; 102206
Hou-xian Du / State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing P.R.China,102206
Guo-ming Ma / State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing P.R.China,102206
The pumped storage power plants (PSPPs) are a special power source with flexible operation modes and various functions, which more and more have been put into operation in recent years. Compared with the traditional plants, the main wiring structure is also different in the PSPPs. Several high-voltage cables of almost one kilometer in length are usually used to connect the ground switching station and the underground main transformers. There are some abnormal or damaged accidents of transformers and high voltage cables. In this paper, we found that the long high-voltage cable and the no-load transformer cause the oscillation in the process of de-energizing. A simulation model is built by ATP-EMTP software. The field measurement of the de-energizing waveform was used to verify the correctness of the APT-EMTP model. The results show that the number of oscillations increased to more than 15 times with a 2000 m high-voltage cable. The oscillations may lead to the transformer and high-voltage cable failures.

 


 