Analysis on tripping accident caused by improper protection measures of transformer neutral point on 110kV double circuit transmission lines
110kV; transformer; the neutral point; lightning flashover; relay protection; tripping accident
全文录用
XIUJUAN CHEN / China Electric Power Research Institute
Paper foucused on the tripping accident of double circuit lines on the same tower caused by lightning flashover of 110 kV transmission lines. Analyses were made for the flashover and fault recording of the protection gap of 110 kV transformer's ungrounded neutral point. Paper determined that the fundamental cause of the accident was that the gap protection mode adopted by transformer's neutral point caused the malfunction of relay protection under lightning overvoltage. Taking 110 kV substation as an example, the lightning overvoltage, switching overvoltage, single-phase grounding and ground-fault overvoltage, non-full-phase switching overvoltage that the neutral point of 110 kV transformer may withstand during operation were calculated. The results showed that the lightning overvoltage, single-phase grounding and ground-fault overvoltage and non-full-phase switching overvoltage may exceed the insulation level of the neutral point of transformer. Protective measures should be taken. The configuration and parameter setting of protective measures must be reasonable. Otherwise tripping accidents or equipment damages would occur and affect the reliability of power supply. The research results have important reference value for 110kV engineering design and transformer protection.
重要日期
  • 会议日期

    04月07日

    2019

    04月10日

    2019

  • 04月10日 2019

    注册截止日期

  • 05月12日 2019

    初稿截稿日期

主办单位
IEEE电介质和电气绝缘协会
中国电工学会工程电介质专业委员会
承办单位
华南理工大学
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询