292 / 2018-11-30 02:20:15
Calculation and Analysis on Mechanical Strength of 500kV Hollow Composite Insulator with Different Types of Grooves on the Surface of End Fitting
hollow composite insulator,mechanical analysis,interfaces
终稿
Haofeng Zhang / Graduate School at Shenzhen, Tsinghua University
Zhidong Jia / Graduate School at Shenzhen, Tsinghua University
Xiaoxing Wei / China Southern Power Grid
The impact of the different types of grooves on mechanical strength of hollow composite insulators has been calculated and analyzed in this paper to find the proper size and distribution. The investigations have shown that stress concentrations appear in the FRP tube and in the end fitting near the top of the interface. Grooves on the interface between end fitting and FRP tube can decrease the maximum stress of adhesive greatly and the most proper size should be 2mm depth, 8.5mm width and 26mm interval. Besides different depths cause the different of the stress concentration.