Field-Line-Circuit Co-Simulation of Lightning Disturbances in Substation Secondary Control Cables Considering Shield Grounding and Differential-Mode Terminal Impedance
编号:183 访问权限:仅限参会人 更新:2026-10-19 18:08:31 浏览:4次 口头报告

报告开始:暂无开始时间(Asia/Shanghai)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
When lightning current enters a substation grounding system, the resulting nonuniform ground-potential rise and transient electromagnetic field can jointly couple into secondary control cables connecting primary equipment to the protection room. This paper establishes a three-dimensional model that includes homogeneous soil, a copper-bar main grounding grid, the secondary equipotential grid in the protection room, the main control and communication building, cable trenches, representative grounded metallic enclosures of primary equipment, and a two-core shielded control cable. A transient source in Schematic excites the three-dimensional field model, which is coupled to a Cable Studio multiconductor transmission-line model and terminal networks to form a field-line-circuit computational chain from the lightning source, grounding-current propagation, and spatial field to the cable and its terminations. With the lightning location and cable route fixed, six cases are defined by combining three shield-grounding configurations with two differential-mode intercore terminal impedances at the protection-room end. The results show that lightning current propagates along the main grid and equipment-grounding branches, producing nonuniform transient surface-current and magnetic-field distributions in the secondary-equipment area. The shield-grounding topology substantially changes the shield return path and current envelope; when a direct grounding path exists at the primary-equipment end, the P7 current reaches the order of 10³ A. For the same grounding topology, changing the protection-room intercore termination from 50 Ω to 10 kΩ does not change the overall shield-current order of magnitude or decay trend. Under the symmetric two-core condition, the two node voltages are strongly synchronous, indicating a pronounced common-mode component and relatively weak differential-mode conversion. The findings provide a reference for shield-grounding design, terminal-boundary analysis, and joint lightning-disturbance modeling of substation secondary control cables.
关键词
substation, lightning electromagnetic disturbance, secondary control cable, cable-shield grounding, differential-mode terminal impedance, field-line-circuit co-simulation.
报告人
Weijie Pan
Master's student Xi'an University of Technology

稿件作者
Chi Chen Xi'an University of Technology
Weijie Pan Xi'an University of Technology
Chuang Wang Xi'an Unversity of Technology
ChengWen Song Xi’an University of Technology
Yumeng Huang Xi'an University of Technology
Jiayi Yang Xi'an University of Technology
发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    11月06日

    2026

    至

    11月08日

    2026

  • 10月15日 2026

    初稿截稿日期

主办单位
IEEE Instrumentation and Measurement Society
承办单位
Sichuan University
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询