Fault-Tolerant Operation of Three-Level ANPC Inverter Drives Using Model Predictive Duty Cycle Control
编号:98 访问权限:仅限参会人 更新:2025-05-06 15:11:52 浏览:9次 口头报告

报告开始:暂无开始时间(Asia/Shanghai)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
This paper presents a novel fault tolerant operation strategy for three-level active neutral point clamped (3L-ANPC) inverter fed permanent magnet synchronous motor (PMSM) drives. Firstly, a thyristor connecting the mid-point of dc-bus voltage and the common-point of bi-directional switches is applied to reconstruct 3L-ANPC inverter topology under fault conditions, thereby avoiding unbalanced neutral-point voltage influence and increasing maximum modulation index. Furthermore, to enhance the PMSM performance, a virtual vector synthesis method is proposed, which also simplifies the duty-cycle calculation of remaining voltage vectors. Simulation results has verified the effectiveness of the proposed More details and experimental results will be presented in the full manuscript.
关键词
active neutral point clamped inverter,,fault tolerant control,model predictive control,duty cycle control,open circuit fault