摘要
When taking earth as part of HVDC system loop, Grounding electrode system is connected to ground effectively, operation mode of which is different from normal HVDC lines. A ±500kV HVDC system model is established in this paper by using PSCAD/EMTDC simulation platform, based on which the fault operation characteristic of grounding electrode line is simulated and analyzed , and a fault location method based on the Bergeron line model aimed at single line grounded short circuit is also put forward in this paper. Head-end voltage and two outlets current after fault are used to calculate voltage distribution along line. According to the characteristics that the fault or electrode point is the minimum voltage along line, the fault location function is established to calculate the fault distance. The simulation result and project instances indicated that the fault of grounding electrode line can be located accurately with the proposed method.
关键词
HVDC;,grounding electrode line,Bergeron line model,fault location,voltage distribution
报告人
Yining Zhang
CSG EHV

稿件作者
Yining Zhang CSG EHV
Xingxing Cheng Jiaxing Power Supply Company State Grid Corporation of China Jiaxing, China
发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    10月21日

    2019

    10月24日

    2019

  • 10月13日 2019

    摘要录用通知日期

  • 10月13日 2019

    初稿截稿日期

  • 10月14日 2019

    初稿录用通知日期

  • 10月24日 2019

    注册截止日期

  • 10月29日 2019

    终稿截稿日期

承办单位
Xi'an Jiaotong University
联系方式
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询