HVDC Startup Strategy in AC/DC Hybrid System Black Start Process
编号:309 访问权限:仅限参会人 更新:2020-11-11 12:10:27 浏览:112次 张贴报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
Reducing the power system restoration time has always been an important topic in power system research. For AC/DC hybrid systems, if the rapid regulation ability of HVDC is utilized in the early stage of black start, the restoration time can be reduced. This paper proposes a HVDC startup strategy while considering HVDC lines and explores their control flexibility in the black start process. The requirement on the minimum short-circuit ratio (SCR) is presented based on the concept of critical short-circuit ratio (CSCR) under non-rated state. The maximum transmittable power of HVDC is obtained using the short-circuit ratio of the system. The feasibility of the proposed HVDC startup strategy is proved through numerical simulation on the IEEE 24-bus test system and the black-start scheme that including HVDC startup can significantly reduce the system restoration time.
关键词
HVDC,power system restoration,restoration time,black start