Study on Operation Characteristics of Wind Power Grid-connected Doubly-Fed AC/DC Hybrid System
编号:21 访问权限:仅限参会人 更新:2020-11-11 12:09:18 浏览:94次 张贴报告

报告开始:暂无开始时间(12)

报告时间:暂无持续时间

所在会场:[暂无会议] [暂无会议段]

暂无文件

摘要
Aiming at the impact of large-scale wind power integration on the operation characteristics of HVDC, this paper builds an AC-DC hybrid double-fed HVDC system including wind power generation. In the PSCAD/EMTDC software, the steady-state and transient operation characteristics of wind power access system are studied. The results show that the system can reach stable operation within 0.2s when the system starts. When the three-phase short-circuit ground fault occurs, the DC voltage and active power of the system show a downward trend, after the 0.05 s fault removal, active power of line gradually restores stability under the action of regulator, but line voltage appears unstable. When one end is disconnected, the voltage and active power on the fault side change to zero instantaneously, and the other end has a small reduction, and then it can resume normal operation.
关键词
Double feed DC transmission system; HVDC; Operating characteristics; Wind power
报告人
Jingjing Wang
Xi'an University of Technology

稿件作者
Jingjing Wang Xi'an University of Technology
Guoqing Yang Xi'an University of Technology
Deyi Wang Xi'an University of Technology
Shujie Zhang State Grid Qinghai Electric Power Company
Yanhe Li State Grid Qinghai Electric Power Company
Yourui Xu State Grid Qinghai Electric Power Company
发表评论
验证码 看不清楚,更换一张
全部评论
重要日期
  • 会议日期

    10月21日

    2019

    10月24日

    2019

  • 10月13日 2019

    摘要录用通知日期

  • 10月13日 2019

    初稿截稿日期

  • 10月14日 2019

    初稿录用通知日期

  • 10月24日 2019

    注册截止日期

  • 10月29日 2019

    终稿截稿日期

承办单位
Xi'an Jiaotong University
联系方式
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询