622 / 2019-03-31 10:09:17
A pilot protection scheme for UHVDC lines based on backward traveling-wave difference
Pilot protection; HVDC lines; Traveling wave; transmission characteristics; high-resistance faults
终稿
Hong Cao / China Electric Power Research Institute
Min Xie / State Grid Anhui electric power company
Zexin Zhou / China Electric Power Research Institute
Xingguo Wang / China Electric Power Research Institute
Bin Yu / State Grid Anhui electric power company
Dingxiang Du / China Electric Power Research Institute
Haigang Wang / State Grid Anhui electric power company
Tongwen Wang / State Grid Anhui electric power company
Yang Yu / State Grid Anhui electric power company
As a backup protection for HVDC lines, legacy current differential protection needs long time delay to avoid the influence of distributed capacitor current under external faults. A new protection principle is proposed based on the fact that under internal faults, the backward traveling wave at the side away from the fault point and the forward traveling wave at the side near the fault point will not satisfy the transmission function of the DC line, whereas the backward traveling wave at the side away from the fault point and the forward traveling wave at the side near the fault point satisfy the transmission function under external faults. The proposed principle is verified in PSCAD/EMTDC, and simulation results show that, it can identify the fault reliably and rapidly, while having better tolerance to high fault resistance.
重要日期
  • 会议日期

    10月21日

    2019

    10月24日

    2019

  • 10月13日 2019

    摘要录用通知日期

  • 10月13日 2019

    初稿截稿日期

  • 10月14日 2019

    初稿录用通知日期

  • 10月24日 2019

    注册截止日期

  • 10月29日 2019

    终稿截稿日期

承办单位
Xi'an Jiaotong University
联系方式
移动端
在手机上打开
小程序
打开微信小程序
客服
扫码或点此咨询